| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | PROVISO: | | | 1. DUCT SMOKE DETECTOR SHALL BE LOCATED | | | IN SUPPLY AIR STREAM PER NFPA 90A 4-4 OR | | | IN THE RETURN AIR DUCT PRIOR TO ANY MIX- | | | ING OF OUTSIDE AIR PER 1997 SMC THE | | | DETAIL ON M-1 SHOWS DUCT DETECTOR NOT | | | SENSING THE RETURN DROP FROM THE STORE | | | ROOM AND THIS HAS TO BE PROTECTED BY THE | | | DUCT DETECTOR ALSO |
|