| Plan Review Notes For Permit 00070034 |
| Permit Number |
00070034 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | ***************PROVISO****************** | | | 1)OVERFLOW LINE SHALL DISCHARGE TO | | | STORM. | | | | | | 2)SUBMIT ALL SECTION DETAILS NOTED ON | | | SHEET W1.3. | | | | | | 3)PIPE SIZES SHOWN ON SHT.W1.3 DON'T | | | CORRELATE W/SIZES NOTED IN DETAIL "C" | | | ON W4.8. | | | | | | 4)SIZE ALL PIPNG ON SHT.W2.2 AND SIZE | | | PIPING ON ALL DETAILS. | | | | | | 5)SUBMIT ALL APPLICABLE SHEETS FOR | | | REVIEW.SOME NOTED DETAILS ARE NOT ON THE | | | PLANS.SUBMIT ALL DETAILS FOR REVIEW ON | | | AS-BUILTS. | | | | | | 6)INDICATE MAKE,MODEL AND TYPE OF | | | BACKFLOW PREVENTION DEVICE SHOWN IN WET | | | WALL FOUNTAIN ROOM. |
|