| 2001-01-08 00:00:00 | FAILED |
| | 1.0 |
| | DRAWINGS SUBMITTED DO NOT SHOW TIE IN |
| | OFF OKEECHOBEE BLVD FOR WATER AND SEWER. |
| | 2.0 |
| | PVC PIPINGAND CONDUITS MUST BE GROUPED |
| | &SLEEVED TOGETHER WHEN CROSSING ROSEMARY |
| | AVENUE.MUST KEEP 1O'MIN AWAY FROM EX. WM |
| | 3.0 |
| | DISCHARGE FROM THE SYSTEM SHALL BE TIED |
| | TO SANITARY SEWER AND NOT TO THE DRAINGE |
| | AS CALLED OUT. |
| | 4.0 |
| | NO METERS OR BACKFLOWS ARE SHOWN IN ANY |
| | DRAWING. |
| | 5.0 |
| | ALL WORK PERFORMED ALONG OKEECHOBEE |
| | BLVD MUST BE DONE UNDER A PERMIT FROM |
| | FDOT. |
| | 6.0 |
| | PLEASE PROVIDE LOCATION OF ALL UTILITES |
| | WHERE TAPPING WILL OCCUR OR ALONG ANY |
| | CITY ROW WHERE WORK WILL BE PERFORM. |
| | THIS WILL AVOID ANY CONFLICTS IN THE |
| | FIELD. |
| | 7.0 |
| | TWO SETS OF PRINTS OF THE TAP WILL HAVE |
| | TO BE SUBMITTED TO MANNY GONZALEZ |
| | CITY OF WEST PALM BEACH 1000 45TH ST |
| | WEST PALM BEACH, FL 33409 |
| | 561-659-8040. |
| | 8.0 |
| | SHOPDRAWINGS WILL BE REQUIRED ON ANY |
| | ITEMS INSTALLED OUT IN THE ROW. SUBMITT |
| | 2 COPIES FOR APPROVAL. |
| | 9.0 |
| | FOR SANITARY SEWER SERVICES A CLEAN-OUT |
| | IS REQUIRED EVERY 75L.F. AND ONE MUST |
| | BE PROVIDED JUST INSIDE OF THE R.O.W. |
| | LINE ON PRIVATE PROPERTY. |
| | 10.0 |
| | PLEASE PROVIDE MORE DETAIL OF WHERE THE |
| | FOUNTAINS FALL WITHIN THE ROW AND EXIST. |
| | UTILIES. |