Plan Review Notes
Plan Review Notes For Permit 00070029
Permit Number 00070029
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00**************** PROVISO **************
  
 1)NOTE: PLEASE SUBMIT PLANS SHOWING ALL
 NEW BRANCH CIRCUITS WITH CORRELATING
 #`S TO REVISED PANEL SCHEDULE.
  
 2)NOTE: PLEASE SUBMIT A REVISED LOAD
 CALCULATION. CONTINUOUS LOADS TO BE FIG.
 AT 125% (LIGHTING ETC. ) ART:220
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW BEFORE ROUGH ELECTRICAL
 INSPECTION IS CALLED IN. IF THERE ARE
 ANY QUESTIONS PLEASE CALL 659-8096 EXT.
 8372.