| Plan Review Notes For Permit 00061786 |
| Permit Number |
00061786 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | 1) PROVIDE FIRE ALARM SYSTEM SHOP | | | DRAWINGS FOR FIRE ALARM EQUIPMENT | | | SHOWN ON POWER PLAN. | | | 2) EXITING THROUGH STOCKROOM PERMITTED | | | IF THE FOLLOWING CONDITIONS EXIST, NOT | | | MORE THAN 50 PERCENT OF EXIT ACCESS | | | IS PROVIDED THROUGH STOCKROOM, AN AISLE | | | OF AT 44" WIDE TO BE PRESENT THROUGH | | | STOCKROOM, THE 44" AISLE IS TO BE | | | MAINTAINED, AND THE STOCKROOM CANNOT | | | BE LOCKED. | | | 3) AN ADDITIONAL EXIT SIGN MAY BE NEEDED | | | TO DIRECT PERSONS TO REAR EXIT DOOR IN | | | STOCKROOM. | | | FIRE PLAN REVIEW CONDUCTED BY ASST. | | | FIRE MARSHAL MIKE CARSILLO |
|