2001-01-08 00:00:00TRUSS DRAWINGS CHECKLIST:
  
 1-ARCHITECT TO REVIEW TRUSS LAYOUT AND
 ENGINEERED TRUSSES AS WELL AND PROVIDE
 REVIEW STAMP WITH THE FIRM LOGO.
 (ARCHITECT IS NOT SUPPOSED TO SEAL
 ENGINEERED DRAWINGS THAT HE DIDN'T DO)
  
 2-ARCHITECT'S FRAMING PLANS AND ANCHOR
 SCHEDULE NEED TO BE COORDINATED WITH
 TRUSS ENGINEERED DRAWINGS.
 - KEYED DETAILS DON'T MATCH ACTUAL
 CONDITIONS. SEE SHEET A-8 AND DETAILS
 SPECIFIED.
 - THERE ARE SEVERAL CONNECTIONS THAT ARE
 NOT SPECIFIED.
  
 NOTE: CLOSELY REVIEW FRAMING PLANS AND
 ENGINEERED TRUSSES AND UPDATE/CLARIFY
 AS REQUIRED TO AVOID UNNECESSARY
 RETURNS.
  
 3-PROVIDE UPLIFT CONNECTOR SCHEDULE FOR
 FLOOR FRAMING TRUSSES.
  
 4-SOME FLOOR TRUSSES ARE MISSING THE
 UPLIFT LOADS CALCULATED.
  
 5-TRUSSES GENERAL DETAILS WERE NOT
 UPDATED AS REQUESTED ON PREVIOUS
 CHECKLIST. SEE PREVIOUS CHECKLIST.
  
 6-ARCHITECT TO DATE ANY DRAWING THAT IS
 SEALED FOR PUBLIC RECORD. FLORIDA
 STATUTES, CHAPTER 481. SEE ATTACHED
 REMAINDER.
  
  
  
 NOTES:
 -IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT 659-8096 EXT. 8232.