2001-01-08 00:00:00TRUSS DRAWINGS CHECKLIST:
 1-ARCHITECT TO REVIEW TRUSS LAYOUT AND
 ENGINEERED TRUSSES AS WELL. THIS WILL
 HELP TO DETERMINE IF CONNECTORS
 SELECTED ARE APPROPRIATE TO RESIST THE
 CALCULATED LOADS.
  
 NOTE: ARCHITECT NEED NOT TO SIGN/SEAL
 TRUSS LAYOUT OR ENGINEERED TRUSSES.
 ONLY THE REVIEW STAMP WITH HIS COMPANY
 LOGO IS REQUIRED SINCE THE TRUSSES ARE
 NOT PREPARED BY THE ARCHITECT.
  
 2-THERE ARE SOME TRUSSES THAT CONNECTORS
 SPECIFIED ARE NOT ABLE TO RESIST THE
 LOADS CALCULATED ON THE ENGINEERED
 TRUSSES.
 -ALSO, CHECK THE BEARING POINTS THAT
 ARE CONSIDERED ON THE ENGINEERED
 TRUSSES AND SPECIFY PROPER CONNECTOR.
 -SEE TRUSS LAYOUT FOR SAMPLE OF TRUSSES
 THAT REQUIRE CONNECTORS TO BE
 SPECIFIED.
 -THERE IS A SLIGHT CHANGE ON THE TRUSS
 LAYOUT AND ARCHITECT'S FRAMING PLAN.
 SPECIFY CONNECTORS AS REQUIRED.
  
 3-CLEARLY SPECIFY CONNECTORS THAT ARE
 WOOD TO WOOD OR CONCRETE TO WOOD.
  
 4-GENERAL TRUSS DETAILS AND LETTERS ARE
 TOO OLD. UPDATE ALL INFORMATION AS
 REQUIRED.
 -NOTE: DATE SHOULD BE THE DATE WHEN
 DOCUMENTS ARE SEALED.
 -CLARIFY WHY THERE ARE GENERAL DETAILS
 WITH THE COPY OF ONE ENGINEER SEAL,
 BUT THEY ARE SIGNED AND SEALED BY
 ANOTHER ENGINEER. WHO'S THE ONE
 RESPONSIBLE FOR PRODUCING SUCH DETAILS