| Plan Review Notes For Permit 00061776 |
| Permit Number |
00061776 |
|
| Review Stop |
R |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | APPROVED WITH PROVISO: | | | 1-PROVIDE PRODUCT APPROVAL FOR: ARCHED | | | WINDOWS (MISSILE IMPACT), FRENCH DOORS | | | WITH SIDELITES ASSEMBLY (MISSILE | | | IMPACT). | | | -PROVIDE COMPLETE MANUFACTURER SPECS, | | | INSTALLATION INSTRUCTIONS, UL LISTED. | | | 2-SECTION/DETAIL AT BALCONY NEEDS MORE | | | INFORMATION. SEE COMMENTS ON PLANS. | | | 3-PROVIDE ATTIC ACCESS AT MAIN ROOF. | | | SECTION 2309.6 SBC 1997. | | | 4-REVISE ROOF FRAMING PLAN AND ANCHOR | | | SCHEDULE AS REQUIRED. CLEARLY SPECIFY | | | WOOD TO WOOD CONNECTORS AND WOOD TO | | | CONCRETE CONNECTORS. SEE COMMENTS. | | | 5-COMPLETELY SPECIFY CEILING CONSTRUCT'N | | | AT FRONT AND REAR PORCHES. INCLUDE | | | FASTENERS TYPES AND SPACING AS PER | | | ASTM C926 AND C1063. SEC 2504 SBC 1997 |
|