| Plan Review Notes For Permit 00061776 |
| Permit Number |
00061776 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | ***************** PROVISO ************** | | | | | | 1)NOTE: PLEASE CORRECT METER CAN SIZE. | | | | | | 2)NOTE: PLEASE INCLUDE COLD WATER PIPE | | | AS PART OF GROUNDING SYSTEM. 250-50 | | | | | | 3)NOTE: PLEASE SEE OUTLET SPACING TO | | | MEET 210-52 | | | | | | 4)NOTE: PLEASE SEE 210-52-H FOR HALLWAY | | | OUTLET SPACING. | | | | | | 5)NOTE: PLEASE HAVE ALL OUTLETS SERVING | | | KITCHEN COUNTERSPACE LABELED AS GFI/ | | | GFI PROTECTED. 210-8-A-6 | | | | | | 6)NOTE: OUTLETS IN GARAGE AND OUTSIDE | | | PER 210-8 | | | | | | 7)NOTE: PLEASE SHOW ALL SMOKE DETECTORS | | | AS REQ`D BY NFPA-72 2-2.1.1.1 INSIDE AND | | | OUTSIDE ALL SLEEPING ROOMS.AND ON EACH | | | LEVEL OF MULTI-LEVEL. | | | 8)NOTE: PLEASE HAVE THE REQ`D BATH(S) | | | CIRCUIT(S) PER 210-11-C-3 LISTED ON | | | PANEL SCHEDULE. | | | | | | 9)NOTE: PLEASE NOTE::: YOU SHOW FOUR | | | A/C SYSTEMS ON PLANS AND ONLY THREE ON | | | PANEL SCHEDULES AND LOAD CALCULATIONS. | | | PLEASE SUBMIT CLARIFICATION ON THIS. | | | 215-5 | | | | | | 10)NOTE: PLEASE SEE 110-26 FOR DISC. | | | CLEARENCE REQ`MENTS. | | | | | | PLEASE SUBMIT ALL THE ABOVE INFORMATION | | | FOR REVIEW BEFORE ANY ROUGH ELECTRICAL | | | INSPECTION IS CALLED IN. IF THERE ARE | | | ANY QUESTIONS PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | 561-659-8096 EXT 8372 |
|