Plan Review Notes
Plan Review Notes For Permit 00061776
Permit Number 00061776
Review Stop E
Sequence Number 2
Notes
Date Text
2001-01-08 00:00:00***************** PROVISO **************
  
 1)NOTE: PLEASE CORRECT METER CAN SIZE.
  
 2)NOTE: PLEASE INCLUDE COLD WATER PIPE
 AS PART OF GROUNDING SYSTEM. 250-50
  
 3)NOTE: PLEASE SEE OUTLET SPACING TO
 MEET 210-52
  
 4)NOTE: PLEASE SEE 210-52-H FOR HALLWAY
 OUTLET SPACING.
  
 5)NOTE: PLEASE HAVE ALL OUTLETS SERVING
 KITCHEN COUNTERSPACE LABELED AS GFI/
 GFI PROTECTED. 210-8-A-6
  
 6)NOTE: OUTLETS IN GARAGE AND OUTSIDE
 PER 210-8
  
 7)NOTE: PLEASE SHOW ALL SMOKE DETECTORS
 AS REQ`D BY NFPA-72 2-2.1.1.1 INSIDE AND
 OUTSIDE ALL SLEEPING ROOMS.AND ON EACH
 LEVEL OF MULTI-LEVEL.
 8)NOTE: PLEASE HAVE THE REQ`D BATH(S)
 CIRCUIT(S) PER 210-11-C-3 LISTED ON
 PANEL SCHEDULE.
  
 9)NOTE: PLEASE NOTE::: YOU SHOW FOUR
 A/C SYSTEMS ON PLANS AND ONLY THREE ON
 PANEL SCHEDULES AND LOAD CALCULATIONS.
 PLEASE SUBMIT CLARIFICATION ON THIS.
 215-5
  
 10)NOTE: PLEASE SEE 110-26 FOR DISC.
 CLEARENCE REQ`MENTS.
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW BEFORE ANY ROUGH ELECTRICAL
 INSPECTION IS CALLED IN. IF THERE ARE
 ANY QUESTIONS PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 561-659-8096 EXT 8372