Plan Review Notes
Plan Review Notes For Permit 00061767
Permit Number 00061767
Review Stop P
Sequence Number 2
Notes
Date Text
2001-01-08 00:00:001)SUBMIT OCCUPANT LOAD BASED ON SQUARE
 FEET OF HABITABLE FLOOR SPACE.SEE SPC
 SEC.407.1.3.FOR ALLOWED DEDUCTIBLE AREAS
  
 2)AN ADDITIONAL LAVATORY IS REQD.IN THE
 WOMEN'S TOILET ROOM PER SPC TABLE 407.
  
 3)GRAB BAR BEHIND WATER CLOSETS SHALL BE
 A MIN.OF 36" PER FACBC SEC.4.16.4.
  
 4)A MIN. OF 29"IS REQD.UNDER LAV.FROM
 FINISH FLOOR TO BOTTOM OF THE APRON.
 FACBC SEC.4.19.2.