| Plan Review Notes For Permit 00061767 |
| Permit Number |
00061767 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | DENIED:********************************* | | | 1.PROVIDE AIR BALANCE SCHEDULE TO SHOW | | | COMPLIANCE WITH 1997 SMC 501.2.. | | | 2.PROVIDE OUTSIDE AIR CALCULATIONS PER | | | ASHRAE 62-89 | | | 3.REQUIRES ENERGY EFFICIENCY RATING PER | | | FL. ENERGY EFFICIENCY CODE. | | | 4.PROVIDE ALL INFOFMATION ON THE AHU | | | UNIT ON SHEET M-2. | | | 5.INDICATE SMOKE DETECTOR PER 1997 SMC | | | 406.1 ON PLANS. | | | 6.REQUIRE DUCT MATERIAL SCHEDULE. | | | 7.PROVIDE EXHAUST FAN DETAIL. |
|