Plan Review Notes
Plan Review Notes For Permit 00061767
Permit Number 00061767
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00************** UNSAT ******************
  
 1)NOTE: AS PER 450-13B TANSFORMER MAY
 NOT BE INSTALLED IN CEILING SPACE ABOVE.
  
 2)NOTE: CLARIFY WHEATER PANEL"A" IS
 200AMPS OR 225AMPS.
  
 3)NOTE:FLOOR PLANS DO ONLY SHOW ONE
 PANEL. RISER SHOW IT TO BE TWO SEPARATE
 SECTIONS.? PLEASE CORRECT.
  
 4)NOTE: PLEASE SEE 220-12 FOR THE REQ`D
 LOAD CALCULATIONS TO BE SHOWN FOR TRACK
 LIGHTING.
  
 5)NOTE: PLEASE LABEL THE TRANSFORMER
 GROUND AS GROUNDING ELECTRODE AND SIZE
 PER 250-66
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  