| Plan Review Notes For Permit 00061767 |
| Permit Number |
00061767 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | ************** UNSAT ****************** | | | | | | 1)NOTE: AS PER 450-13B TANSFORMER MAY | | | NOT BE INSTALLED IN CEILING SPACE ABOVE. | | | | | | 2)NOTE: CLARIFY WHEATER PANEL"A" IS | | | 200AMPS OR 225AMPS. | | | | | | 3)NOTE:FLOOR PLANS DO ONLY SHOW ONE | | | PANEL. RISER SHOW IT TO BE TWO SEPARATE | | | SECTIONS.? PLEASE CORRECT. | | | | | | 4)NOTE: PLEASE SEE 220-12 FOR THE REQ`D | | | LOAD CALCULATIONS TO BE SHOWN FOR TRACK | | | LIGHTING. | | | | | | 5)NOTE: PLEASE LABEL THE TRANSFORMER | | | GROUND AS GROUNDING ELECTRODE AND SIZE | | | PER 250-66 | | | | | | PLEASE SUBMIT ALL THE ABOVE INFORMATION | | | FOR REVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | 561-659-8096 EXT 8372 |
|