| Plan Review Notes For Permit 00061747 |
| Permit Number |
00061747 |
|
| Review Stop |
R |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | APPROVED WITH PROVISO: | | | 1-PROVIDE SAFETY GLASS AT BEDROOM #2. | | | SECTION 2405.2 SBC 1997. | | | 2-SPECIFY SIZES OF CEILING FANS AS PER | | | TABLE 6-6 OF FLORIDA ENERGY EFFICIENCY | | | CODE FOR BUILDING CONSTRUCTION,1997 ED | | | 3-PROVIDE PRODUCT APPROVAL FOR: | | | -DOUBLE INSWING ENTRY DOORS. | | | -FIREPLACE MEETING THE REQUIREMENTS OF | | | UL 127. AND SECTION 2806 SBC 1997. | | | -BUTT GLAZING ASSEMBLY. | | | -WINDOW MULLIONS. | | | -TRANSOM WINDOW WITH THE SIZE AS SHOWN | | | ABOVE SLIDING GLASS DOORS AT LIVING RM | | | -FRENCH DOOR AT MASTER SUITE. | | | 4-PROVIDE COMPLETE DETAIL/SPECIFICATIONS | | | FOR CEILING CONSTRUCTION AT FRONT AND | | | BACK PORCHES. | | | NOTE: INCLUDE FASTENER TYPE & SPACING. | | | SECTION 2504 SBC 1997. | | | 5-SEE PLANS FOR ADDITIONAL COMMENTS, | | | INCLUDING COMMENTS BY THE OTHER TRADES | | | 6-COMPLETELY SPECIFY INSTALLATION OF | | | AHU IN ATTIC. INCLUDING THE HANGERS. |
|