2001-01-08 00:00:00CHECKLIST:
 1-PAY IMPACT FEES.
 2-PROVIDE SAFETY GLASS AT BEDROOM #2.
 SECTION 2405.2 SBC 1997.
 3-REVISE ENERGY CALCULATIONS:
 -THERE ARE FOUR BEDROOMS, NOT THREE,
 SEE ARCHITECT'S PLANS.
 4-SPECIFY SIZES OF CEILING FANS AS PER
 TABLE 6-6 OF FLORIDA ENERGY EFFICIENCY
 CODE FOR BULDING CONSTRUCTION, 1997 ED
 5-PROVIDE PRODUCT APPROVAL FOR:
 -DOUBLE INSWING ENTRY DOORS.
 -FIREPLACE UL APPROVAL.
 -SLIDING GLASS DOORS WITH THE SIZE
 SHOWN AT LIVING ROOM.
 -BUTT GLAZING ASSEMBLY.
 -WINDOW MULLIONS.
 -TRANSOM WINDOW WITH THE SIZE AS SHOWN
 ABOVE SLIDING GLASS DOORS AT LIVING RM
 -FRENCH DOOR AT MASTER SUITE.
 6-CLARIFY CONSTRUCTION AT ENTRY DOORS:
 IS THERE A PRECAST LINTEL BETWEEN THE
 ENTRY DOORS AND ROUND TRANSOM ABOVE OR
 DOORS AND TRANSOM ARE PART OF THE SAME
 ASSEMBLY ?. IF SO, THEN NEED TO
 PROVIDE THE REQUIRED PRODUCT APPROVAL.
 7-PROVIDE DETAIL/SPECIFICATIONS FOR
 CEILING CONSTRUCTION AT FRONT AND BACK
 PORCHES. INCLUDING FASTENERS TYPES AND
 SPACING. SECTION 2504 SBC 1997.
 8-SEE PLANS FOR ADDITIONAL COMMENTS,
 INCLUDING COMMENTS BY THE OTHER TRADES
 9-COMPLETELY SPECIFY INSTALLATION OF
 AHU IN ATTIC. INCLUDING THE HANGERS.
 10-OWES $199.39 TO THE CITY FOR LOW
 VALUATION AND RADON FEES.
  
  
 IF YOU HAVE ANY QUESTIONS PLEASE FEEL
 FREE TO CONTACT JULIO GOMEZ AT 659-8096
 EXTENSION 8232.