Plan Review Notes
Plan Review Notes For Permit 00061704
Permit Number 00061704
Review Stop R
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00DENIED
  
 1)PROVIDE 2 CURRENT COPIES OF METRO-DADE
 OR SBCCI PRODUCT APPROVALS FOR SPECIFIC
 EXTERIOR WINDOWS AND DOORS TO BE USED.
  
 2)MISSLE IMPACT PROTECTION IS REQUIRED
 FOR ALL EXTERIOR GLAZING.CITY OF WPB
 AMENDMENTS TO THE 97 SBC SEC.1606.4.
 PROVIDE 2 COPIES OF METRO-DADE OR SBCCI
 PRODUCT APPROVALS,KEY PLAN AND INSTALL-
 ATION SCHEDULE WITH SPECIFIC TYPE ANCHOR
 TO BE USED FOR STORM PANELS.
  
 3)SUBMIT 2 COMPLETED CITY OF WPB DESIGN
 COMPLIANCE FORMS.1997 SBC OR ASCE 7-95.
  
 4)FL ENERGY EFFICIENCY CODE FORMS 600A-
 97 MUST BE SIGNED BY OWNER/AGENT.
  
 5)INDICATE ON PLANS LOCATION OF ATTIC
 ACCESS AND ATTIC VENTILATION. 97 SBC
 2309.6 AND 2309.7
  
 6)FINISH FLOOR ELEVATION MUST BE MINIMUM
 OF 6" ABOVE BASE FLOOD ELEVATION. CITY
 CODE CHAPTER 12. PROJECT IS LOCATED IN
 A5 FLOOD ZONE EL 7.
  
 7)IMPACT FEES MUST BE PAID TO PALM BEACH
 COUNTY,PLANS STAMPED BY THEM AND A COPY
 OF THE RECIEPT SUBMITTED TO CITY OF WPB
 BUILDING DEPT. BEFORE A PERMIT TO
 CONSTRUCT WILL BE ISSUED.
  
 8)SAFETY GLASS IS REQUIRED IN THE
 WINDOWS ADJACENT TO DOORS C AND D ON
 PLAN. 97 SBC 2405.2.1
  
 9)INDICATE ON PLANS METHODS OF
 ATTACHMENT TO BE USED TO CONNECT STUDS
 TO TOP PLATES AND WOOD COLUMNS TO WOOD
 HEADERS.