| Plan Review Notes For Permit 00061693 |
| Permit Number |
00061693 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | *************** UNSAT ***************** | | | | | | 1)NOTE: PLEASE SEE ME-1, PLEASE NOTE | | | YOU SHOW NO OVERCURRENT PROTECTION FOR | | | A/C UNIT STARTER/DISC. PLEASE GIVE | | | CLARIFICATION. #12`S ARE SHOWN WITH | | | 100 AMP OCP AT MAIN DISCONNECT. | | | | | | 2)NOTE: PLEASE SEE ORIG NOTES FOR TRACK | | | LIGHTING CALCULATIONS PER 220-12B | | | | | | 3)NOTE: PLEASE SEE 210-62 FOR SHOW WIND- | | | -OW RECEPTS. YOU SHOW ON SAME CIRCUITS | | | WITH WALL OUTLETS. ALSO SEE 220-12A | | | | | | 4)NOTE" PLEASE INDICATE SQ FT IN LOAD | | | CALC. PER 220-3-A | | | | | | PLEASE SUBMIT ALL THE ABOVE INFORMATION | | | FOR REVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|