2001-01-08 00:00:00*************** UNSAT *****************
  
 1)NOTE: PLEASE SEE ME-1, PLEASE NOTE
 YOU SHOW NO OVERCURRENT PROTECTION FOR
 A/C UNIT STARTER/DISC. PLEASE GIVE
 CLARIFICATION. #12`S ARE SHOWN WITH
 100 AMP OCP AT MAIN DISCONNECT.
  
 2)NOTE: PLEASE SEE ORIG NOTES FOR TRACK
 LIGHTING CALCULATIONS PER 220-12B
  
 3)NOTE: PLEASE SEE 210-62 FOR SHOW WIND-
 -OW RECEPTS. YOU SHOW ON SAME CIRCUITS
 WITH WALL OUTLETS. ALSO SEE 220-12A
  
 4)NOTE" PLEASE INDICATE SQ FT IN LOAD
 CALC. PER 220-3-A
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  