| Plan Review Notes For Permit 00061693 |
| Permit Number |
00061693 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | 1) NO FIRE SPRINKLER PLANS OR HYDRAULIC | | | CALCULATIONS PROVIDED. | | | 2) WRONG FIRE CODE REFERENCE, SHOULD | | | READ NFPA 101, 1985 EDITION INSTEAD OF | | | NFPA 101, 1991 EDITION. | | | 3) LOWER SOFFIT IN ENTRY AT 7'-1 AFF | | | NOT PROPER. HEADROOM IN MEANS OF EGRESS | | | SHALL BE 7'-6 OR 6'-8 IF PROJECTED FROM | | | CEILING. PLEASE EXPLAIN SOFFIT. | | | 4) EXITING PERMITTED THRU STOCKROOM ONLY | | | IF, NOT MORE THAN 50 PERCENT OF THE | | | OCCUPANT LOAD PERMITTED THROUGH | | | STOCKROOM.AISLE TO BE AT LEAST 44" WIDE | | | AND MAINTAINED IN AN UNOBSTRUCTED | | | CONDITION. | | | 5) INTERIOR FINISH TO BE CLASS A OR B. | | | 6) ENSURE EMERGENCY LIGHTING IS PROVIDED | | | IN STOCKROOM. | | | 7) FIRE EXTINGUISHERS REQUIRED. |
|