Plan Review Notes
Plan Review Notes For Permit 00061693
Permit Number 00061693
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00**************** UNSAT *****************
  
 1)NOTE: PLEASE SUBMIT A ONE LINED FOR
 ELETRICAL SERVICE. NO SERVICE SHOWN.??
  
 2)NOTE:SUBMIT AIC RATINGS FOR ALL MAINS/
 PANELS. ALL EQUIPMENT MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT. 110-9
  
 3)NOTE: PLEASE SUBMIT LOAD CALCULATIONS.
 TO INCLUDE ALL CONTINUOUS LOADS AT 125%
 (LIGHTING ETC ) PER 220
 SHOW LOAD CALCULATIONS COMPLETED. 215-5
  
 4)NOTE: PLEASE SEE 220-12 FOR ALL TRACK
 LIGHTING LOADS TO BE SHOWN.
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS