| Plan Review Notes For Permit 00061693 |
| Permit Number |
00061693 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | **************** UNSAT ***************** | | | | | | 1)NOTE: PLEASE SUBMIT A ONE LINED FOR | | | ELETRICAL SERVICE. NO SERVICE SHOWN.?? | | | | | | 2)NOTE:SUBMIT AIC RATINGS FOR ALL MAINS/ | | | PANELS. ALL EQUIPMENT MUST BE RATED FOR | | | THE AVAILABLE FAULT CURRENT. 110-9 | | | | | | 3)NOTE: PLEASE SUBMIT LOAD CALCULATIONS. | | | TO INCLUDE ALL CONTINUOUS LOADS AT 125% | | | (LIGHTING ETC ) PER 220 | | | SHOW LOAD CALCULATIONS COMPLETED. 215-5 | | | | | | 4)NOTE: PLEASE SEE 220-12 FOR ALL TRACK | | | LIGHTING LOADS TO BE SHOWN. | | | | | | PLEASE SUBMIT ALL THE ABOVE INFORMATION | | | FOR REVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL . | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | 561-659-8096 EXT 8372 |
|