Plan Review Notes
Plan Review Notes For Permit 00061693
Permit Number 00061693
Review Stop B
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00 
  
  
 1. SUBMIT LETTER FROM SPECIAL INSPECTOR
 2. FIRE SPRINKLER PERMIT MUST BE ISSUED
 PRIOR TO ISSURANCE OF PERMIT.
 3. BUILDING IS TYPE 2 CONSTRUCTION
 1997 SBC.
 4. FIRE MARSHALL TO GIVE DIRECTION OF
 FIRE EXTINGUISHER TYPE AND LOCATION.
 5. TITLE PAGE-GOVERNING CODES-CORRECT-
 SEE M/P/FP COMMENTS FOR LISTING
 6. PARTITION DETAIL 11A ON A.IA-TENTANT
 DEMISING WALL REQUIRED TO BE 1HR.
 RATED PROVIDE UL NUMBER.ASSEMBLY
 REQUIRED TO BE COMPLETED PRIOR TO C.O
 ONE SIDE COMPLETED AS SHOWN IS
 UNACCEPTABLE PER DETAIL.
 7. PROVIDE PRODUCT APPROVAL FOR
 HURRICANE SHUTTERS, SHOW LOCATION
 WHERE SHUTTERS ARE TO BE STORED, IF
 SHUTTERS STACKED ON END, SHUTTERS TO
 BE DESINGED FOR ADDITIONAL LOADING.
 8. COMPLY TO TABLE 407 OF THE SPC,
 SUBMIT SQUARE FOOTAGE OF HABITABLE
 FLOOR SPACE. REFER TO SECTION 407.1.3
 FOR ALLOWED DEDUCTIBLE AREAS.