| Plan Review Notes For Permit 00061693 |
| Permit Number |
00061693 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | | | | | | | | | | 1. SUBMIT LETTER FROM SPECIAL INSPECTOR | | | 2. FIRE SPRINKLER PERMIT MUST BE ISSUED | | | PRIOR TO ISSURANCE OF PERMIT. | | | 3. BUILDING IS TYPE 2 CONSTRUCTION | | | 1997 SBC. | | | 4. FIRE MARSHALL TO GIVE DIRECTION OF | | | FIRE EXTINGUISHER TYPE AND LOCATION. | | | 5. TITLE PAGE-GOVERNING CODES-CORRECT- | | | SEE M/P/FP COMMENTS FOR LISTING | | | 6. PARTITION DETAIL 11A ON A.IA-TENTANT | | | DEMISING WALL REQUIRED TO BE 1HR. | | | RATED PROVIDE UL NUMBER.ASSEMBLY | | | REQUIRED TO BE COMPLETED PRIOR TO C.O | | | ONE SIDE COMPLETED AS SHOWN IS | | | UNACCEPTABLE PER DETAIL. | | | 7. PROVIDE PRODUCT APPROVAL FOR | | | HURRICANE SHUTTERS, SHOW LOCATION | | | WHERE SHUTTERS ARE TO BE STORED, IF | | | SHUTTERS STACKED ON END, SHUTTERS TO | | | BE DESINGED FOR ADDITIONAL LOADING. | | | 8. COMPLY TO TABLE 407 OF THE SPC, | | | SUBMIT SQUARE FOOTAGE OF HABITABLE | | | FLOOR SPACE. REFER TO SECTION 407.1.3 | | | FOR ALLOWED DEDUCTIBLE AREAS. |
|