| Plan Review Notes For Permit 00061675 |
| Permit Number |
00061675 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | 1)RM.123-DOOR CANNOT SWING INTO CLEAR | | | FLOOR SPACE REQD.FOR THE LAVATORY PER | | | FACBC SEC.4.22.2. | | | | | | 2)SINK IN CONCESSION AREA SHALL BE H.C. | | | ACCESSIBLE PER FACBC SEC.4,24.1-4.24.7. | | | | | | 3)FLOOR DRAINS ARE REQD.IN THE TOILET | | | ROOMS PER SPC SEC.409.4.1.1. | | | | | | 4)WALLS AND FLOORS IN TOILET ROOMS SHALL | | | BE NONABSORBENT PER SBC SEC.1204.2. | | | | | | 5)SHOW REQD.WHEELCHAIR TURNING SPACE IN | | | TOILET ROOMS PER FACBC SEC.4.2.3. | | | | | | 6)PLANS SHOW WOMEN'S TOILET ROOM IN | | | ELECTRONICS RETAIL SALES AREA.CLEARLY | | | SHOW HOW MALE PATRONS WILL HAVE FREE | | | ACCESS TO MALE TOILET ROOM. | | | | | | 7)NOTE OCCUPANT LOAD ON PLANS USING SPC | | | TABLE 407 AS A GUIDE.SEE SPC SEC.407.1.3 | | | FOR ALLOWED DEDUCTIBLE AREAS. | | | | | | 8)CALCULATED AIR CHAMBERS SHALL COMPLY | | | W/SPC SEC.607.8.3,607.8.4.IF USED. | | | | | | 9)SHT.P-3-PROVIDE SHIP'S LADDER IN | | | CONJUNCTION W/PLATFORM FOR WATER HEATER | | | PER SPC 501.7. | | | CALL 561-659-8096,EXT.8377 IF YOU HAVE | | | QUESTIONS. | | | TIMOTHY LARGE | | | PLUMBING PLANS EXAMINER. |
|