2001-01-08 00:00:00PLUMBING PLAN REVIEW
 (1)SHT.A.1 SPC 94 MIN FACILITIES,TAB 407
 MEN1 W/C WOMEN 2 W/C
 MEN1 LAV WOMEN 2 LAVS
 DRINKING FOUNTAIN 1
 REST RM'S TO COMPLY W/FACBC 4.1.3 (11)
 D/F TO COMPLY WITH 4.1.3 (10) PROVISIONS
 SHALL BE MADE FOR PEOPLE WHO HAVE
 TROUBLE BENDING OR STOOPING.
 (2)SHT P0.1 ICE MACHINE DETAIL,
 SEPERATE CUBBER DRAIN & ICE BIB DRAIN.
 SPC 94 SEC 606.1 CROSSCONNECTION
 (3) SHT P-3 WATER HEATER TO BE READLY
 ACCESSIBLE SPC 94 SEC 501.7 RELOCATE TO
 FLOOR OR PROVIDE A FIXED SHIPS LADDER &
 WORKING PLATFORM.
 (4) SHT P3-1SHOW LOCATION OF BACK
 FLOW PREVENTER AS REQUIRED BY LOCAL
 ORDINANCE #2853-95
  
 (5) SHT P0.1 GAS WATER HEATER DETAIL
 DIELECTRIC UNIONS NOT APPROVED IN WATER
 SUPPLY SYSTEM,USE DIELECTRIC NIPPLES OR
 COUPLINGS.SPC 94 SEC 611.2 MATERIALS A/G
 (6) SHT P0.1 IF DETAILS SHOWN,DO NOT
 APPLY,DELETE OR VOID THEM.
 END OF COMMENTS