| Plan Review Notes For Permit 00061675 |
| Permit Number |
00061675 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | PLUMBING PLAN REVIEW | | | (1)SHT.A.1 SPC 94 MIN FACILITIES,TAB 407 | | | MEN1 W/C WOMEN 2 W/C | | | MEN1 LAV WOMEN 2 LAVS | | | DRINKING FOUNTAIN 1 | | | REST RM'S TO COMPLY W/FACBC 4.1.3 (11) | | | D/F TO COMPLY WITH 4.1.3 (10) PROVISIONS | | | SHALL BE MADE FOR PEOPLE WHO HAVE | | | TROUBLE BENDING OR STOOPING. | | | (2)SHT P0.1 ICE MACHINE DETAIL, | | | SEPERATE CUBBER DRAIN & ICE BIB DRAIN. | | | SPC 94 SEC 606.1 CROSSCONNECTION | | | (3) SHT P-3 WATER HEATER TO BE READLY | | | ACCESSIBLE SPC 94 SEC 501.7 RELOCATE TO | | | FLOOR OR PROVIDE A FIXED SHIPS LADDER & | | | WORKING PLATFORM. | | | (4) SHT P3-1SHOW LOCATION OF BACK | | | FLOW PREVENTER AS REQUIRED BY LOCAL | | | ORDINANCE #2853-95 | | | | | | (5) SHT P0.1 GAS WATER HEATER DETAIL | | | DIELECTRIC UNIONS NOT APPROVED IN WATER | | | SUPPLY SYSTEM,USE DIELECTRIC NIPPLES OR | | | COUPLINGS.SPC 94 SEC 611.2 MATERIALS A/G | | | (6) SHT P0.1 IF DETAILS SHOWN,DO NOT | | | APPLY,DELETE OR VOID THEM. | | | END OF COMMENTS |
|