| Plan Review Notes For Permit 00061675 |
| Permit Number |
00061675 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | DENIED:********************************* | | | 1.PROVIDE DAMPER LOCATION PER 1997 SMC | | | 610.1.2.ALSO DAMPER DETAIL. | | | 2.PROVIDE AIR BALANCE SCHEDULE TO SHOW | | | COMPLIANCE WITH 1997 SMC 501.2.. | | | 3.PROVIDE OUTSIDE AIR SCHEDULE PER | | | ASHRAE 62-89. | | | 4.REQUIRE DUCT MATERIAL SCHEDULE. | | | 5.REQUIRE FLEX DUCT CONNECTION DETAIL. | | | 6.LOCAL CODE REQUIRES MIN. 18" OF CLEAR- | | | ANCE BETWEEN ROOF SURFACE AND BOTTOM OF | | | SUPPORT BEAM OF STAND. |
|