2001-01-08 00:00:00DENIED:*********************************
 1.PROVIDE DAMPER LOCATION PER 1997 SMC
 610.1.2.ALSO DAMPER DETAIL.
 2.PROVIDE AIR BALANCE SCHEDULE TO SHOW
 COMPLIANCE WITH 1997 SMC 501.2..
 3.PROVIDE OUTSIDE AIR SCHEDULE PER
 ASHRAE 62-89.
 4.REQUIRE DUCT MATERIAL SCHEDULE.
 5.REQUIRE FLEX DUCT CONNECTION DETAIL.
 6.LOCAL CODE REQUIRES MIN. 18" OF CLEAR-
 ANCE BETWEEN ROOF SURFACE AND BOTTOM OF
 SUPPORT BEAM OF STAND.