| Plan Review Notes For Permit 00061675 |
| Permit Number |
00061675 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | *************** UNSAT ****************** | | | | | | 1)NOTE: PLEASE COMPLETE LOAD CALCULATION | | | -S. SHOW ALL CONTINUOUS LOADS AT 125% | | | (LIGHTING) ETC. | | | ALSO SHOW TRACK LIGHTING FIGURED INTO | | | CALCS PER 220-12 | | | | | | 2)NOTE: PLEASE SEE 210-62 FOR SHOW | | | WINDOW RECEPT REQ`MENTS AND TO BE | | | CALCULATED PER 220-12 | | | | | | 3)NOTE: ALL ELECTRICAL BEING SHOWN ON | | | FLOOR PLAN,,, IS ALL THIS NEW? WHAT IS | | | EXISTING? KITCHEN AREA? | | | | | | 4)NOTE: PLEASE NOTE OUTLETS IN KITCHEN | | | AND BATH AREA TO BE GFI/GFI PROTECTED. | | | PER 210-8 | | | | | | | | | PLEASE SUBMIT ALL THE ABOVE INFORMATION | | | FOR REVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 659-8096 EXT 8372 |
|