| Date |
Text |
| 2001-01-08 00:00:00 | CHECKLIST: |
| | 1-PAY IMPACT FEES TO PALM BEACH COUNTY. |
| | 2-REVISE LOAD REQUIREMENTS FOR ATTIC |
| | STORAGE. 30 PSF LIVE LOAD. SEE TABLE |
| | 1604.1 SBC 1997. |
| | 3-PROVIDE SAFETY GLASS AS REQUIRED AT |
| | FAMILY ROOM, LIVING ROOM AND MASTER |
| | BATH. SECTION 2405.2 SBC 1997. |
| | 4-PROVIDE COMPLETE AHU HANGING DETAILS. |
| | INCLUDE FASTENERS TYPES AND SIZES. |
| | DETAIL SHOWN ON SHEET A5 DOESN'T APPLY |
| | TO THIS HOUSE. SECTION 104.2.2 CITY |
| | AMENDMENTS TO SBC 1997. |
| | 5-PROVIDE COMPLETE SPECIFICATIONS/DETAIL |
| | FOR CEILING CONSTRUCTION AT ENTRY AND |
| | REAR PORCHES. INCLUDE FASTENERS TYPES |
| | AND SPACING. SECTION 2504 SBC 1997. |
| | 6-FOOTING F2 TO HAVE 16" MINIMUM IN |
| | DEPTH AS PER SECTION 1804.1.9 OF CITY |
| | AMENDMENTS AND SEC. 1804.1.3 SBC 1997. |
| | 7-ROOF FRAMING PLAN: SOME TRUSS GIRDERS |
| | ARE SHOWN WITHOUT A SUPPORTING POST TO |
| | TRANSFER THE LOAD TO THE FOOTING. |
| | SPECIFY POSTS AND TOP AND BOTTOM |
| | CONNECTORS. VERIFY IF CONCRETE PAD |
| | REQUIRED TO CARRY THE LOAD. |
| | SECTION 104.2.2 CITY AMENDMENTS. |
| | 8-PROVIDE DETAIL/SPECS SHOWING HOW ARE |
| | OPENINGS DESIGNED TO RECEIVESTORM |
| | PANELS. DRAWINGS SHOW PRECAST LINTELS, |
| | BUT WHAT ABOUT WINDOW SILLS? |
| | THIS WILL DETERMINE THE TYPE OF ANCHOR |
| | AND SPACING REQUIRED TO INSTALL THE |
| | STORM PANEL. |
| | 9-PROVIDE COMPLETE DETAIL/SPECS FOR |
| | CONSTRUCTION OF ARCHED OPENINGS. |
| | SECTION 104.2.2 CITY AMENDMENTS. |
| | 10-PROVIDE SURVEY SHOWING NEW BUILDING |
| | LAYOUT. |
| | 11-PROVIDE SOIL TEST REPORT AS PER SEC. |
| | 1804.2.7.3 OF CITY AMENDMENTS. |
| | 12-PROVIDE COMPLETE BUCK DETAILS FOR |
| | INSTALLATION OF DOORS AND WINDOWS. |
| | INCLUDING THE STRUCTURAL BUCK DETAIL |
| | FOR GARAGE DOORS AND SGD POCKET TYPE. |
| | NOTE: SEE PRODUCT APPROVALS FOR |
| | REQUIRED BUCK SIZE. |
| | 13-STORM PANELS: |
| | -CLARIFY WHICH PRODUCT APPROVAL IS |
| | GOING TO BE USED. SBCCI OR DADE COUNTY |
| | AND PROVIDE COMPLETE DRAWINGS FOR |
| | EITHER ONE. |
| | -SBCCI PRODUCT APPROVAL REPORT AND |
| | DRAWINGS DON'T MATCH. SEE PAGE TWO OF |
| | PRODUCT APPROVAL FOR APPROVED DRAWINGS |
| | -PROVIDE A COMPLETE INSTALLATION SCHED. |
| | AS PER CITY SAMPLE ATTACHED AND KEY |
| | PLAN. |
| | NOTE: KEEP IN MIND THAT ANCHOR TYPE |
| | AND SPACING IS TO BE SELECTED ACCORD'G |
| | TO THE DESIGN PRESSURES,EDGE DISTANCE, |
| | PANEL SPAN, MEAN ROOF HEIGHT,CONNECT'N |
| | TYPE AND STRUCTURE TO BE ATTACHED TO. |
| | (THIS BUILDING IS MASONRY CONSTRUCTION |
| | NOT 3000PSF CONCRETE). |
| | 14-PROVIDE CURRENT PRODUCT APPROVAL FOR: |
| | BUTT GLAZING SYSTEM AS SHOWN ON PLANS, |
| | GARAGE DOORS (DADE COUNTY OR SBCCI, NO |
| | BROWARD COUNTY), SLIDING GLASS DOORS |
| | (POCKET TYPE AS SHOWN ON PLANS), FIXED |
| | WINDOWS OF SIZES AS SHOWN ON LIVING RM |
| | AND FAMILY RM,WINDOW MULLIONS, ARCHED |
| | WINDOWS, ENTRY DOORS (IF SITE SPECIFIC |
| | THEN THE PRODUCT APPROVAL FORM SHALL |
| | BE SIGNED, SEALED AND DATED BY THE |
| | COMPANY ENGINEER AND BY THE ARCHITECT |
| | OF RECORD. PROVIDE LEGIBLE FORMS). |
| | 15-SEE ADDTIONAL COMMENTS ON PLANS, |
| | INCLUDING COMMENTS BY THE OTHER TRADES |
| | 16-HIGHLIGHT FASTENING METHOD AND SYSTEM |
| | TO BE USED IN ROOF TILE PRODUCT APP'L. |
| | |
| | |
| | |
| | NOTE: |
| | -PLEASE RETURN REVIEWED SET OF PLANS |
| | AFTER CORRECTIONS ARE DONE TO THE |
| | ORIGINAL DRAWINGS IN ORDER TO EXPEDITE |
| | THE REVIEW PROCESS. |