| Plan Review Notes For Permit 00061611 |
| Permit Number |
00061611 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | 1)PROVIDE GAS ISOMETRIC FOR REVIEW.SEE | | | ATTACHED REQS.FOR PLAN REVIEW. | | | | | | 2)SHT.P-5.DELETE REFERENCE TO UPC.PLUMB- | | | ING INSTALLATION SHALL COMPLY W/STANDARD | | | PLUMBING CODE 1994 EDITION. | | | | | | 3)SHT.P-5.GREASY WASTE SHALL COMPLY W/ | | | SPC SEC.921 FOR HORIZONTAL COMBINATION | | | WASTE AND VENT SYSTEM.(A REFERENCE NOTE | | | ON THE PLAN DOESN'T CORRECT THE | | | VIOLATIONS IN THE DESIGN.) | | | | | | CALL 561-659-8096,EXT.8377 IF YOU HAVE | | | ANY QUESTIONS. | | | TIMOTHY LARGE | | | PLUMBING PLANS EXAMINER. |
|