Plan Review Notes
Plan Review Notes For Permit 00061611
Permit Number 00061611
Review Stop P
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00PLUMBING PLAN REVIEW
 (1) SHT A1.2 H/C REST RM, TO COMPLY WITH
 FACBC 4.16.2 FIG 28,TURNING RADIUS RUNS
 INTO DOOR, MOVE LAV FOR 36" CLEARANC OF
 WALL,TO ALLOW TURNING RADIUS TO CLEAR
 DOOR SWING.
 (2) SHT P2 DISHWASHER 21 TO BY PASS G/W,
 AND CONNECT TO SANITARY SEWER , LOCAL
 ORDINANCE FOR REGIONAL SEWER PLANT.
 (3) SHT P2 NOTE "H" ALL INDIRECT WASTE,
 FLOOR SINKS.NO F/D'S
 (3) SHT P3GEN NOTE #7 CONDENSATE
 DRAIN FROM COOLER, FLR SINK,NO F/D.
 (4) SHT P4 WTR HTR, DIELECTRIC UNIONS
 NOT APPROVED, USE DIELECTRIC NIPPLES OR
 COUPLINGS SPC SEC 611.2 MATERIALS A/G.
 (5) SHT P4 PROVIDE GAS ISMETRIC, SHOW
 TOTAL DEVELOPED LGTH,TOT. BTU'S, BTU'S
 OF EA APPLIANCE, TYPE OF PIPING MATERIAL
 GAS PSI USED. SGC 97 SEC 104.2
 (6) SHT P6 G/W WASTE & VENT,
 HORIZONTAL DRY VENTS NOT PERMITED,USE
 SPC 94 SEC921 COMBINATION WASTE, VENT.
 SEE ILLUSTRATION PG 275 SPC 94.
 (7) SEE OTHER COMMENTS BY CPPR.
 END OF COMMENTS