| Plan Review Notes For Permit 00061611 |
| Permit Number |
00061611 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | PLUMBING PLAN REVIEW | | | (1) SHT A1.2 H/C REST RM, TO COMPLY WITH | | | FACBC 4.16.2 FIG 28,TURNING RADIUS RUNS | | | INTO DOOR, MOVE LAV FOR 36" CLEARANC OF | | | WALL,TO ALLOW TURNING RADIUS TO CLEAR | | | DOOR SWING. | | | (2) SHT P2 DISHWASHER 21 TO BY PASS G/W, | | | AND CONNECT TO SANITARY SEWER , LOCAL | | | ORDINANCE FOR REGIONAL SEWER PLANT. | | | (3) SHT P2 NOTE "H" ALL INDIRECT WASTE, | | | FLOOR SINKS.NO F/D'S | | | (3) SHT P3GEN NOTE #7 CONDENSATE | | | DRAIN FROM COOLER, FLR SINK,NO F/D. | | | (4) SHT P4 WTR HTR, DIELECTRIC UNIONS | | | NOT APPROVED, USE DIELECTRIC NIPPLES OR | | | COUPLINGS SPC SEC 611.2 MATERIALS A/G. | | | (5) SHT P4 PROVIDE GAS ISMETRIC, SHOW | | | TOTAL DEVELOPED LGTH,TOT. BTU'S, BTU'S | | | OF EA APPLIANCE, TYPE OF PIPING MATERIAL | | | GAS PSI USED. SGC 97 SEC 104.2 | | | (6) SHT P6 G/W WASTE & VENT, | | | HORIZONTAL DRY VENTS NOT PERMITED,USE | | | SPC 94 SEC921 COMBINATION WASTE, VENT. | | | SEE ILLUSTRATION PG 275 SPC 94. | | | (7) SEE OTHER COMMENTS BY CPPR. | | | END OF COMMENTS |
|