Plan Review Notes
Plan Review Notes For Permit 00061611
Permit Number 00061611
Review Stop B
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00 
  
  
  
  
  
  
  
 1. PROVIDE PRODUCT APPROVAL FOR IMPACT
 RESISTANT WINDOWS & DOORS FOR STOREFRONT
 METRO DADE COUNTY OR SBCCI SSTD12-97
 2. SUBMIT FIRE SPRINKLER APPLICATION AND
 PLANS.FIRE SPRINKLER PERMIT MUST BE
 ISSUED PRIOR TO BUILDING PERMIT BEING
 ISSUED.
 3. SIGNS SHALL BE UNDER SEPERATE PERMIT.
 4. SHEET S-1 GENERAL NOTES REFERS TO
 1994 SBC MUST BE 1997 SBC.
 5. SUBMIT DETAIL SHOWING TENANT FIRE
 SEPERATION UL RATING PER 1997 SBC
 CHAPTER 7 TABLE 704.1. TENANT SEPERATION
 WALL TO BE COMPLETED PRIOR TO C.O. BEING
 ISSUED.
 6. ALL WOOD USED IN FRAMING SHALL BE
 FIRE RESISTANT TREATED TO COMPLY WITH
 1997 SBC CHAPTERS 6&7.
 7. HEALTH DEPARTMENT APPROVAL REQUIRED
 PRIOR TO PERMIT BEING ISSUED.