| Plan Review Notes For Permit 00061597 |
| Permit Number |
00061597 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | TOILET ROOM DOORS CANNOT SWING INTO THE | | | CLEAR FLOOR SPACE REQD.FOR THE WATER | | | CLOSET.FACBC SEC.4.22. | | | | | | 2)A DRINKING FOUNTAIN IS REQD.PER SPC | | | TABLE 407.DRINKING FOUNTAIN SHALL COMPLY | | | W/FACBC SEC.4.1.3(10)(A),4.15. | | | | | | 3)HANDICAP TOILET ROOM SHALL BE | | | INDELIBLY POSTED FOR THE INTENDED USE. | | | FACBC SEC.4.1.2(7),4.1.3.(16)(A). | | | | | | 4)HANDICAP TOILET ROOMS SHALL BE LOCATED | | | ON AN ACCESSIBLE ROUTE PER FACBC SECS. | | | 4.1.3(11),4.2.1,4.3.1,4.3.2(3),4.3.3. | | | ACCESIBLE ROUTE SHALL BE CLEARLY DEFINED | | | ON THE PLANS. | | | | | | 5)DOORS ON ACCESSIBLE ROUTE SHALL COMPLY | | | W/FACBC SEC.4.13. | | | | | | 6)TOILET FACILITIES SHALL BE AVAILABLE | | | TO PATRONS WITHOUT RESTRICTION DURING | | | NORMAL OPERATING HOURS PER SPC SEC. | | | 407.2.2. | | | | | | 7)SHOW MOUNTING HEIGHTS & CLEARANCES | | | OF ALL HANDICAP FIXTURES AND APPURTEN- | | | ANCES.COMPLY W/FACBC. | | | | | | 8)MIN.SIZE WATER SUPPLY TO FIXTURES | | | SHALL BE 1/2" PER SPC TABLE 607. | | | | | | 9)HUB DRAIN CANNOT CONNECT TO FLOOR | | | DRAIN AS DRAWN.CONNECT TO FIXTURE DRAIN. | | | SPC 804.5,806. |
|