Plan Review Notes
Plan Review Notes For Permit 00061597
Permit Number 00061597
Review Stop P
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00TOILET ROOM DOORS CANNOT SWING INTO THE
 CLEAR FLOOR SPACE REQD.FOR THE WATER
 CLOSET.FACBC SEC.4.22.
  
 2)A DRINKING FOUNTAIN IS REQD.PER SPC
 TABLE 407.DRINKING FOUNTAIN SHALL COMPLY
 W/FACBC SEC.4.1.3(10)(A),4.15.
  
 3)HANDICAP TOILET ROOM SHALL BE
 INDELIBLY POSTED FOR THE INTENDED USE.
 FACBC SEC.4.1.2(7),4.1.3.(16)(A).
  
 4)HANDICAP TOILET ROOMS SHALL BE LOCATED
 ON AN ACCESSIBLE ROUTE PER FACBC SECS.
 4.1.3(11),4.2.1,4.3.1,4.3.2(3),4.3.3.
 ACCESIBLE ROUTE SHALL BE CLEARLY DEFINED
 ON THE PLANS.
  
 5)DOORS ON ACCESSIBLE ROUTE SHALL COMPLY
 W/FACBC SEC.4.13.
  
 6)TOILET FACILITIES SHALL BE AVAILABLE
 TO PATRONS WITHOUT RESTRICTION DURING
 NORMAL OPERATING HOURS PER SPC SEC.
 407.2.2.
  
 7)SHOW MOUNTING HEIGHTS & CLEARANCES
 OF ALL HANDICAP FIXTURES AND APPURTEN-
 ANCES.COMPLY W/FACBC.
  
 8)MIN.SIZE WATER SUPPLY TO FIXTURES
 SHALL BE 1/2" PER SPC TABLE 607.
  
 9)HUB DRAIN CANNOT CONNECT TO FLOOR
 DRAIN AS DRAWN.CONNECT TO FIXTURE DRAIN.
 SPC 804.5,806.