| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | ***********DENIED*********************** | | | 1. (PGAL)PROVIDE AIR BALANCE COOLING, | | | HEATING CALCULATIONS | | | 2.(PGAL) PROVIDE DETAILS ON THE FOLLOW- | | | ING ITEMS: | | | DUCTWORK MOUNTING DETAILS | | | CONDENSATE TRAP MOUNTING DETAIL | | | CONDENSATE EMERGENCY PLAN | | | 3. (PGAL) CLARIFY IF FIRE DAMPERS ARE | | | REQUIRED PER SMC 610 | | | 4. PROVIDE OUTSIDE AIR CALCULATIONS PER | | | ASHRAE 62-89 |
|