| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | ************* UNSAT ******************* | | | | | | 1)NOTE: PLEASE SUBMIT COMPLETED LOAD | | | CALCULATIONS. SHOW ALL CONTINUOUS LOADS | | | AT 125%. | | | | | | 2)NOTE: PLEASE SHOW TRACK LIGHTING CALCS | | | PER 220-12 A/B SHOW WINDOW LIGHTING. | | | | | | 3)NOTE: PLEASE CLARIFY LOAD ON TRANS- | | | -FORMER, ON PANEL "A". | | | | | | 4)NOTE: OUTLET SPACING TO MEET LOCAL | | | CODE. INCLUDING ALL STORAGE AREAS EVERY | | | 20` OF WALL SPACE. | | | | | | PLEASE SUBMIT ALL THE ABOVE INFORMATION | | | FOR REVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | 561-659-8096 EXT 8372 |
|