Plan Review Notes
Plan Review Notes For Permit 00061597
Permit Number 00061597
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00************* UNSAT *******************
  
 1)NOTE: PLEASE SUBMIT COMPLETED LOAD
 CALCULATIONS. SHOW ALL CONTINUOUS LOADS
 AT 125%.
  
 2)NOTE: PLEASE SHOW TRACK LIGHTING CALCS
 PER 220-12 A/B SHOW WINDOW LIGHTING.
  
 3)NOTE: PLEASE CLARIFY LOAD ON TRANS-
 -FORMER, ON PANEL "A".
  
 4)NOTE: OUTLET SPACING TO MEET LOCAL
 CODE. INCLUDING ALL STORAGE AREAS EVERY
 20` OF WALL SPACE.
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 561-659-8096 EXT 8372