| Plan Review Notes For Permit 00061597 |
| Permit Number |
00061597 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | | | | 1. SUBMIT FLORIDA ENERGY SHEETS SIGNED | | | AND SEALED BY ENGINEER AND SIGNED BY | | | OWNER/AGENT. | | | 2. SUBMIT LETTER FROM SPECIAL INSPECTOR | | | RELEASING SPACE. | | | 3. PROVIDE PRODUCT APPROVAL INFORMATION | | | ON STOREFRONT INDICATING COMPLIANCE WITH | | | 1997 SBC CHAPTER 16 AS AMENDEDED BY WPB | | | OR METRO DADE COUNTY SBCCI PRODUCTS ARE | | | ACCEPTABLE. | | | 4. SIGNS TO BE PERMITED UNDER SEPERATE | | | PERMIT. | | | 5. SUBMIT APPLICATION AND PLANS FOR FIRE | | | SPRINKLER. FIRE SPRINKLER TO BE ISSUED | | | PRIOR TO BUILDING PERMIT. | | | 6. PROVIDE DETAILS ON DEMISING WALL- | | | FIRE RATING AND UL NUMBERS- ALL DEMISING | | | WALL SHALL BE FINISHED BOTH SIDES PRIOR | | | TO C.O. BEING ISSUED. | | | 7. SHEET A2 DECK DETAILS - DEFINE | | | LOCATION LOADING AND ACCESS TO COMPLY | | | WITH 1997 SBC. | | | 8.DEFINE WALL AND RATING AT REAR OF | | | LIMIT AND DOOR SWING IF THIS IS AN EXIT. |
|