| Plan Review Notes For Permit 00061576 |
| Permit Number |
00061576 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | SUBMIT MANUF.SHEETS FOR ALL EQUIPMENT. | | | EQUIPMENT SHALL BE LISTED/APPROVED PER | | | SGC SEC.402.1,NFPA 54 SEC.5.1.1. | | | | | | A UNION IS REQD.DOWNSTREAM OF S.O.V.PER | | | NFPA SEC.5.5.4. | | | | | | CLEARLY IDENTIFY THE SECTIONS OF PIPE | | | ON THE RISER ACCORDING TO THE PIPING | | | CALCULATIONS ON THE SHEETS WITH THE | | | MUELLER FORMULA. |
|