Plan Review Notes
Plan Review Notes For Permit 00061543
Permit Number 00061543
Review Stop B
Sequence Number 2
Notes
Date Text
2001-01-08 00:00:00SUBMITTAL REVIEW COMMENTS
  
 1]
 ENGINEERS CALCULATIONS ARE FOR THE STORM
 PANELS,ALSO ASCE 7-88 IS NOT CURRENT,USE
 ASCE 7-95 AND DESIGN FOR THE GLAZING.
 2]
 SUBMIT CURRENT TEST REPORT FOR STORM
 PANELS.
 3]
 SUBMIT TEST REPORTS FOR WIND AND IMPACT
 PROTECTION FOR NEW GLAZING PANELS.
 4]
 ALL SHOP DRAWINGS AND REPORTS SUBMITTED
 SHALL BE REVIEWED AND APPROVED BY THE
 PROJECT DESIGN PROFESSIONAL.
  
  
  
 REVIEWED BY;
 LUIS MARTINEZ
 561-659-8096
 #8456