2001-01-08 00:00:00PLUMBING PLAN REVIEW
 (1) SHT A-2 WOMENS REST ROOM STALL IS
 REQUIRED TO HAVE A LAV IN THE STALL,
 FACBC 4.17.3 (1 EX NEW CONST )
 (2) SHT A-2 WATER HEATER TO BE READLY
 ACCESSIBLE SPC 94 SEC 501.7, OPTION,
 RELOCATE TO THE FLOOR OR PROVIDE A FIXED
 SHIPS LADDER,WITH A WORKING PLATFORM.
 (3)SHT M-2 FLR DRAIN IN PUBLIC REST RM,
 SPC 94 SEC 409.1.1 TRAP PRIMER REQUIRED.
 (4) SHT M-2 BACK FLOW LOCATION & TYPE TO
 COMPLY W/LOCAL ORDINANCE # 2853-95,
 RPZV W/INDRECT DRAIN,MAX HGTH 48" AFF.
 END OF COMMENTS