| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | *************** UNSAT ****************** | | | | | | 1)NOTE:PLEASE SEE THE REQ`MENTS FOR | | | SHOW WINDOW REC. PER 210-62 AND LOAD | | | CALCULATIONS PER 220-12 | | | | | | 2)NOTE: NEED TO MEET THE REQ`MENTS FOR | | | OUTLETS IN STORAGE AREA PER LOCAL CODE. | | | 20` OF WALL SPACE AND OUTLETS FOR | | | SHOW ROOM AREA ALONG FIXED GLASS PANELS. | | | | | | 3)NOTE: PLEASE SUBMIT LOAD CALCULATIONS | | | SHOWING ALL CONTINUOUS LOADS AT 125% | | | (LIGHTING, CASH REG. ETC. | | | PLEASE CHECK THE LOAD BEING INTRODUCED | | | TO PANEL "A". THIS WILL CHANGE TOTAL | | | LOAD ON PANEL 'B' | | | | | | PLEASE SUBMIT THE ABOVE INFORMAITION | | | FOR REVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | 659-8096 EXT 8372 |
|