| Plan Review Notes For Permit 00061542 |
| Permit Number |
00061542 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | 1)SUBMIT A FLOOR PLAN THAT CLEARLY | | | REFLECTS THE ENTIRE SCOPE OF PLUMBING | | | WORK BEING DONE.SHOW LOCATIONS OF ALL | | | PLUMBING FIXTURES(INCLUDING FUTURE | | | FIXTURES.) | | | | | | 2)ONLY 2 FIXTURES PERMITTED TO BE | | | SUPPLIED BY 1/2" C.W.LINE. | | | | | | 3)DRY VENTS NOT PERMITTED PER SPC SEC. | | | 906.2.1. | | | | | | 4)WATER SUPPLY CONTROL SHALL COMPLY W/ | | | SPC 610.4.2. | | | | | | 5)SHOW DIMENSIONS OF TOILET ROOM.SHOW | | | COMPLIANCE W/FACBC SEC.4.16,4.19. | | | | | | 6)A DRINKING FOUNTAIN WILL BE REQD.PER | | | SPC TABLE 407 AND SHALL COMPLY W/FACBC | | | SEC.4.1.3(10)(A),4.15.PROVISIONS SHALL | | | BE MADE FOR PEOPLE WHO HAVE TROUBLE | | | BENDING OR STOOPING. | | | | | | 7)SUBMIT DETAILS/MOUNTING HEIGHTS OF ALL | | | HANDICAP FIXTURES AND APPURTENANCES. | | | COMPLY W/FACBC-OCT.1997 EDITION. | | | | | | 8)ALL NOTATIONS SHALL BE IN INK,NOT | | | PENCIL. |
|