2001-01-08 00:00:00*************** UNSAT ******************
  
 1)NOTE: PLEASE SUBMIT PLANS WITH ALL
 BRANCH CIRCUIT #`S ON FLOOR PLAN. PLEASE
 SUBMIT PANEL SCHEDULES TO CORRELATE WITH
 FLOOR PLAN.
  
 2)NOTE: PLEASE SHOW LOADS ON HOUSE PANEL
 215-5
  
 3)NOTE: PLEASE SHOW WIRE SIZES FOR RISER
 DIAGRAM. SIZE FOR LOAD OF SERVICE.
  
 4)NOTE: PLEASE SHOW COLD WATER PIPE AS
 PART OF GROUNDING ELECTRODE SYSTEM. 250-
 -50.215-5
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,CALL.
  