| 2001-01-08 00:00:00 | *************** UNSAT ****************** | | | | | | 1)NOTE: PLEASE SUBMIT PLANS WITH ALL | | | BRANCH CIRCUIT #`S ON FLOOR PLAN. PLEASE | | | SUBMIT PANEL SCHEDULES TO CORRELATE WITH | | | FLOOR PLAN. | | | | | | 2)NOTE: PLEASE SHOW LOADS ON HOUSE PANEL | | | 215-5 | | | | | | 3)NOTE: PLEASE SHOW WIRE SIZES FOR RISER | | | DIAGRAM. SIZE FOR LOAD OF SERVICE. | | | | | | 4)NOTE: PLEASE SHOW COLD WATER PIPE AS | | | PART OF GROUNDING ELECTRODE SYSTEM. 250- | | | -50.215-5 | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS,CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 659-8096 EXT 8372 |
|