| Plan Review Notes For Permit 00061502 |
| Permit Number |
00061502 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | 1) PROVIDE FIRE ALARM SYSTEM SHOP | | | DRAWINGS FOR THE FIRE ALARM DEVICES | | | SHOWN ON PLANS. A PLAN AND PERMIT | | | REQUIRED PRIOR TO INSTALLATION. | | | 2) EXITING ALLOWED THROUGH STOCKROOM | | | IF THE FOLLOWING CONDITIONS ARE MET, | | | NOT MORE THAN 50 PERCENT OF EXIT | | | ACCESS IS PROVIDED THROUGH STOCKROOM, | | | DOOR LEADING INTO STOCKROOM CANNOT | | | BE LOCKED, AISLE TO BE A MINIMUM OF | | | 44" IN THE CLEAR, AND SAID AISLE TO | | | BE MAINTAINED AT 44" AT ALL TIMES. | | | 3) FLOOR PLAN INDICATES TWO OFFICES | | | 104 AND 105. IS 105 GOING TO BE USED | | | FOR STOCK. |
|