| 2001-01-08 00:00:00 | 1)DOOR 101 SHALL COMPLY W/FACBC SEC. | | | 4.13.6.(SEE EWC)SAME FOR DOOR 102 AT | | | RESTROOM #106. | | | | | | 2)H.C.DRESSING ROOM SHALL COMPLY W/FACBC | | | SEC.4.35.4.-BENCH TO BE LOCATED ALONG | | | LONGER WALL. | | | | | | 3)WATER CLOSETS AND FIXTURE BRANCHES NOT | | | PERMITTED ON WET VENTS.SUBMIT REVISED | | | SANITARY RISER PRIOR TO PLBG.INSPECTION. | | | COUNTYWIDE AMENDMENTS TO SPC SEC.911.1.1 | | | | | | 4)WATER HEATER SHALL BE LISTED.SPC SEC. | | | 503.3. | | | | | | 5)HANDICAP ACCESSIBLE TOILET ROOMS SHALL | | | BE INDELIBLY POSTED FOR THE INTENDED | | | USE,BE ON AN ACCESSIBLE ROUTE AND | | | AVAILABLE TO PATRONS WITHOUT RESTRICTION | | | DURING NORMAL OPERATING HOURS.FACBC SECS | | | 4.1.3,4.1.2,4.2.1.,4.3.1. 4.3.2.,4.3.3. | | | ACCESIBLE ROUTE SHALL BE CLEARLY DEFINED | | | ON THE PLANS. | | | | | | CALL 561-659-8096 IF YOU HAVE ANY | | | QUESTIONS. |
|