Plan Review Notes
Plan Review Notes For Permit 00061500
Permit Number 00061500
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:001) REAR DOOR LEADING FROM SALES AREA
 DOES NOT SWING IN THE DIRECTION OF EXIT
 TRAVEL.
 2) PROVIDE FIRE ALARM SHOP DRAWINGS FOR
 FIRE ALARM EQUIPMENT SHOWN ON POWER
 PLAN.
 3) NO NOTE ON PLANS INDICATING THAT THE
 FIRE SPRINKLER SYSTEM IS CALCULATED
 TO EXISTING FIRE SPRINKLER CALCULATIONS.