| Date |
Text |
| 2001-04-26 00:00:00 | 1) PLANS DO NOT INDICATE THE VOLUME, | | | HEIGHT OR WIDTH OF THE TANK. IT IS | | | PRESUMED THAT THE TANK WILL CONTAIN | | | LIQUID OXYGEN. PLEASE PROVIDE ELEVATION | | | DRAWINGS OF THE OXYGEN TANK. | | | 2) NO PIPING OR APPURTENANT EQUIPMENT | | | SHOWN TO OR FROM THE TANK. | | | 3) NO WARNING SIGNS OR LABELS | | | IDENTIFYING THE HAZARD OR MATERIAL | | | THAT IS PLANNED FOR STORAGE. | | | 4) NO SITE PLAN PROVIDED FOR THE | | | INSTALLATION AREAS. | | | 5) ON THE PREVIOUS APPROVED PLANS THE | | | TWO DOORS LEADING INTO THE SCREEN | | | ENCLOSURE WERE DESIGNATED AS EXIT DOORS. | | | PLEASE EXPLAIN EXITING ARRANGEMENT. | | | 6) THE SCREEN ENCLOSURE HAS NO PERMIT | | | TO BE CONSTRUCTED. ALL EXTERIOR WORK | | | WAS TO BE DONE UNDER SEPARATE PERMIT. | | | 7) WHERE DID THE ORIGINAL PROPOSED | | | NITROGEN TANK GO. | | | | | | CAPTAIN MIKE CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 |
|