| Plan Review Notes For Permit 00061481 |
| Permit Number |
00061481 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | ****************PROVISO***************** | | | 1)SHT A3.1-BACKFLOW PREVENTERS LOCATED | | | IN VAULTS SHALL COMPLY W/SPC SEC.606.4.1 | | | LOCATION SHALL BE APPROVED BY UTILITIES | | | DEPT. | | | | | | 2)OVERFLOW DRAINAGE SYSTEM FOR THE ROOF | | | SHALL BE DESIGNED ON 1994 EDITION OF THE | | | SPC SEC.1109 & APPENDIX "A". | | | | | | 3)STORM WATER SYSTEM SHALL BE SHOWN ON | | | CIVIL DRAWINGS AND SIZED PER TABLES | | | 1108.1 & 1108.2 OF THE SPC. | | | | | | *****NOTE:REVISED DRAWINGS SHALL BE | | | SUBMITTED PRIOR TO ISSUANCE OF PLUMBING | | | PERMIT. |
|