| Plan Review Notes For Permit 00061381 |
| Permit Number |
00061381 |
|
| Review Stop |
FS |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | 1) FIRE DEPARTMENT CONNECTION SHALL BE | | | LOCATED NO MORE THAN 150 FEET FROM A | | | FIRE HYDRANT. | | | 2) PROVIDE SPARE HEAD BOX AND WRENCH | | | FOR FIRE SPRINKLER SYSTEM. | | | 3) COVERED WALKWAY IF COMBUSTIBLE | | | AND LARGER THAN 4 FEET WIDE, IS TO BE | | | FIRE SPRINKLER PROTECTED. |
|