| 2001-01-08 00:00:00 | PLUMBING PLAN REVIEW OF COMMENTS | | | DATED 09-19-00 NOT APPROVED,PAUL SCHMITZ | | | (1) SHT P-4,P-2 WTR HTR IS LOCATED ON | | | FLOOR T/P, P/D TERMINATE TO FLOOR SINK | | | IN JANITORS CLOSET #208. | | | (3) SHT P-8 SHOWS AAV VENTS IN ATTIC | | | SPC 94 SEC 904.1.3 MIN.OF ONE 3"VTR. | | | (5) SHT P-2 SHOW DETAIL OF CONDENSATE | | | OVER FLOW AS BUILT. (NO GOOSENECK) | | | (7) SHT P-3 SHOWS THE REQ WHEEL CHAIR | | | TURNING SPACE IN RM # 216,219 INFRINGING | | | IN WATER CLOSET SPACE. FACBC 4.2.3 | | | (9) SAME AS NOTE (1) WTR HTR TO BE | | | READLY ACCESSIBLE. SHOW AS BUILT. | | | END OF COMMENTS 561-659-8096 X 8233 |
|