2001-01-08 00:00:00PLUMBING PLAN REVIEW OF COMMENTS
 DATED 09-19-00 NOT APPROVED,PAUL SCHMITZ
 (1) SHT P-4,P-2 WTR HTR IS LOCATED ON
 FLOOR T/P, P/D TERMINATE TO FLOOR SINK
 IN JANITORS CLOSET #208.
 (3) SHT P-8 SHOWS AAV VENTS IN ATTIC
 SPC 94 SEC 904.1.3 MIN.OF ONE 3"VTR.
 (5) SHT P-2 SHOW DETAIL OF CONDENSATE
 OVER FLOW AS BUILT. (NO GOOSENECK)
 (7) SHT P-3 SHOWS THE REQ WHEEL CHAIR
 TURNING SPACE IN RM # 216,219 INFRINGING
 IN WATER CLOSET SPACE. FACBC 4.2.3
 (9) SAME AS NOTE (1) WTR HTR TO BE
 READLY ACCESSIBLE. SHOW AS BUILT.
 END OF COMMENTS 561-659-8096 X 8233