Plan Review Notes
Plan Review Notes For Permit 00061369
Permit Number 00061369
Review Stop E
Sequence Number 6
Notes
Date Text
2001-01-11 00:00:00*****************UNSAT ****************
  
 1)NOTE: PLEASE SEE E-7 PLEASE NOTE
 MISSING OUTLET FOR EQUIPMENT PER
 MECHANICAL CODE 309.2 AND NEC 210-63.
  
 2)NOTE: PLEASE SEE E-8 PLEASE PLACE NOTE
 ON PLANS FOR CEILING TO REMAIN OPEN TO
 MEET NEC 450-13 (A,B). FOR TRANSFORMER
 INSTALLATION.
  
 3)NOTE: PLEASE SEE E-10PANEL"2 AC.
 PLEASE CORRELATE LOAD/WIRE SIZE/BRKR
 AND CONDUIT TO MEET NEC.
  
  
 PLEASE REVISE THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW.
 561--659-8096 EXT 8372