| Notes |
| Date |
Text |
| 2001-01-11 00:00:00 | *****************UNSAT **************** | | | | | | 1)NOTE: PLEASE SEE E-7 PLEASE NOTE | | | MISSING OUTLET FOR EQUIPMENT PER | | | MECHANICAL CODE 309.2 AND NEC 210-63. | | | | | | 2)NOTE: PLEASE SEE E-8 PLEASE PLACE NOTE | | | ON PLANS FOR CEILING TO REMAIN OPEN TO | | | MEET NEC 450-13 (A,B). FOR TRANSFORMER | | | INSTALLATION. | | | | | | 3)NOTE: PLEASE SEE E-10PANEL"2 AC. | | | PLEASE CORRELATE LOAD/WIRE SIZE/BRKR | | | AND CONDUIT TO MEET NEC. | | | | | | | | | PLEASE REVISE THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW. | | | 561--659-8096 EXT 8372 |
|