| 2001-01-08 00:00:00 | 1)WATER HEATERS SHALL BEREADILY |
| | ACCESSIBLE.SPC SEC.501.7. |
| | |
| | 2)THE MIN.SIZE GAS LINE TO ITEMS P-14, |
| | P-16,P-17 SHALL BE 1 1/4" PER SGC TABLE |
| | 305.4(A). |
| | |
| | 3)THE SANITARY SYSTEM REQUIRES ONE MAIN |
| | VENT STACK OR STACK VENT THROUGH THE |
| | ROOF (MIN.3")SPC 904.3.1. |
| | |
| | 4)DESIGN OF DRAINAGE SYSTEM FOR GREASY |
| | WASTE SYSTEM SHALL COMPLY W/SPC SEC.921 |
| | FOR HORIZONTAL COMBINATION WASTE AND |
| | VENT SYSTEM. |
| | |
| | 5)AN OVERFLOW IS REQD.ON THE CONDENSATE |
| | SYSTEM PRIOR TO THE CONNECTION WITH THE |
| | STORM DRAINAGE SYSTEM OR CONNECTION |
| | SHALL BE INDIRECT.SPC SEC.804.3,806. |
| | |
| | 6)SHT.A2.2-APPEARS TO SHOW FLOOR DRAINS |
| | LOCATED IN THE MECHANICAL ROOM.LOCATION |
| | OF FLOOR DRAINS SHALL COMPLY W/SPC SEC. |
| | 409.4.4.1. |
| | |
| | 7)SHT.A2.3-SHOW THE REQD.WHEELCHAIR |
| | TURNING SPACE IN THE TOILET ROOMS #216, |
| | 219.COMPLY W/FACBC SEC.4.2.3.THE TURNING |
| | SPACE THAT IS CURRENTLY SHOWN HAS THE |
| | WATER CLOSET INFRINGING COMPLETELY INTO |
| | THE SPACE. |
| | |
| | 8)CLARIFY THE AREA WHERE THE GAS PIPING |
| | PENETRATES THE EXTERIOR WALL INTO THE |
| | BUILDING.WHAT IS THE USE OF THIS SPACE? |
| | |
| | 9)ADDENDUM TO COMMENT #1-SUPPLY A SHIP'S |
| | LADDER AND PLATFORM OR RELOCATE WATER |
| | HEATER TO FLOOR. |
| | |