2001-01-08 00:00:001)WATER HEATERS SHALL BEREADILY
 ACCESSIBLE.SPC SEC.501.7.
  
 2)THE MIN.SIZE GAS LINE TO ITEMS P-14,
 P-16,P-17 SHALL BE 1 1/4" PER SGC TABLE
 305.4(A).
  
 3)THE SANITARY SYSTEM REQUIRES ONE MAIN
 VENT STACK OR STACK VENT THROUGH THE
 ROOF (MIN.3")SPC 904.3.1.
  
 4)DESIGN OF DRAINAGE SYSTEM FOR GREASY
 WASTE SYSTEM SHALL COMPLY W/SPC SEC.921
 FOR HORIZONTAL COMBINATION WASTE AND
 VENT SYSTEM.
  
 5)AN OVERFLOW IS REQD.ON THE CONDENSATE
 SYSTEM PRIOR TO THE CONNECTION WITH THE
 STORM DRAINAGE SYSTEM OR CONNECTION
 SHALL BE INDIRECT.SPC SEC.804.3,806.
  
 6)SHT.A2.2-APPEARS TO SHOW FLOOR DRAINS
 LOCATED IN THE MECHANICAL ROOM.LOCATION
 OF FLOOR DRAINS SHALL COMPLY W/SPC SEC.
 409.4.4.1.
  
 7)SHT.A2.3-SHOW THE REQD.WHEELCHAIR
 TURNING SPACE IN THE TOILET ROOMS #216,
 219.COMPLY W/FACBC SEC.4.2.3.THE TURNING
 SPACE THAT IS CURRENTLY SHOWN HAS THE
 WATER CLOSET INFRINGING COMPLETELY INTO
 THE SPACE.
  
 8)CLARIFY THE AREA WHERE THE GAS PIPING
 PENETRATES THE EXTERIOR WALL INTO THE
 BUILDING.WHAT IS THE USE OF THIS SPACE?
  
 9)ADDENDUM TO COMMENT #1-SUPPLY A SHIP'S
 LADDER AND PLATFORM OR RELOCATE WATER
 HEATER TO FLOOR.
  
 CALL 561-659-8096,EXT.8377 IF YOU HAVE
 QUESTIONS.
 TIMOTHY LARGE
 PLUMBING PLANS EXAMINER.