Plan Review Notes
Plan Review Notes For Permit 00061369
Permit Number 00061369
Review Stop FIRE
Sequence Number 4
Notes
Date Text
2001-01-08 00:00:001) OCCUPANT LOAD TO BE DETERMINED BY
 THIS OFFICE.
 2) PLEASE PROVIDE FLAMESPREAD DATA ON
 BLUEBOARD AND SONASPRAY FINISH FOR
 CEILING.
 3) STANDPIPE LOCATIONS STILL NOT SHOWN
 ON PLANS.
 4) ALL DOORS SUBJECT TO AN OCCUPANCY
 OF 100 OR MORE PERSONS SHALL BE
 PROVIDED WITH APPROVED PANIC HARDWARE.
 FIRE DOORS SHALL BE EQUIPPED WITH
 APPROVED FIRE EXIT PANIC HARDWARE.
 5) PROVIDE FLAMESPREAD DATA ON
 PROJECTION SCREEN.
 6) PROVIDE MORE DETAILS ON TELESCOPING
 BLEACHER.
 7) PLEASE IDENTIFY REQUIRED AISLES ON
 PAGES FFS.2 AND FFS.3. TABLES AND
 CHAIRS CANNOT BLOCK EXIT ACCESS TO
 EXITS.
 8) GAS INSTALLATION TO COMPLY WITH
 NFPA 54.
 9) DRY-CHEMICAL FIRE SUPPRESSION SYSTEM
 NOT ALLOWED. ONLY WET-CHEMICAL FIRE
 SUPPRESSION SYSTEMS PERMITTED.
 APPROVED PROVISO: