| Plan Review Notes For Permit 00061369 |
| Permit Number |
00061369 |
|
| Review Stop |
FIRE |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | 1) OCCUPANT LOAD TO BE DETERMINED BY | | | THIS OFFICE. | | | 2) PLEASE PROVIDE FLAMESPREAD DATA ON | | | BLUEBOARD AND SONASPRAY FINISH FOR | | | CEILING. | | | 3) STANDPIPE LOCATIONS STILL NOT SHOWN | | | ON PLANS. | | | 4) ALL DOORS SUBJECT TO AN OCCUPANCY | | | OF 100 OR MORE PERSONS SHALL BE | | | PROVIDED WITH APPROVED PANIC HARDWARE. | | | FIRE DOORS SHALL BE EQUIPPED WITH | | | APPROVED FIRE EXIT PANIC HARDWARE. | | | 5) PROVIDE FLAMESPREAD DATA ON | | | PROJECTION SCREEN. | | | 6) PROVIDE MORE DETAILS ON TELESCOPING | | | BLEACHER. | | | 7) PLEASE IDENTIFY REQUIRED AISLES ON | | | PAGES FFS.2 AND FFS.3. TABLES AND | | | CHAIRS CANNOT BLOCK EXIT ACCESS TO | | | EXITS. | | | 8) GAS INSTALLATION TO COMPLY WITH | | | NFPA 54. | | | 9) DRY-CHEMICAL FIRE SUPPRESSION SYSTEM | | | NOT ALLOWED. ONLY WET-CHEMICAL FIRE | | | SUPPRESSION SYSTEMS PERMITTED. | | | APPROVED PROVISO: |
|