| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | 1)THE LAYOUT OF THE RESTROOMS ON THE | | | LIFE SAFETY PLANS DOESN'T CORRELATE WITH | | | THE OTHER SHEETS.COUNTYWIDE AMENDMENTS | | | TO SPC SEC.104.2.1. | | | | | | 2)WATER HEATERS SHALL BE READILY ACCESS- | | | IBLE PER SPC SEC.501.7.SUPPLY FIXED | | | LADDER AND PLATFORM OR RELOCATE WATER | | | HEATER TO FLOOR. | | | | | | 3)A UNION SHALL BE INSTALLED DOWNSTREAM | | | OF THE MANUAL SHUTOFF VALVE BY THE | | | SOLENOID VALVE ON THE GAS SYSTEM PER | | | NFPA 54 SEC.5.5.4.(S.O.V.IS SHOWN AS | | | SOLENOID VALVE.CLARIFY.) | | | | | | 4)THE MIN.SIZE GAS LINE TO ITEMS P-14, | | | P-16,P-17 SHALL BE 1 1/4" PER SGC TABLE | | | 305.4(A). | | | | | | 5)THE SANITARY SYSTEM REQUIRES ONE MAIN | | | VENT STACK OR STACK VENT THROUGH THE | | | ROOF(MIN.3").SPC 904.3.1. | | | | | | 6)DESIGN OF DRAINAGE SYSTEM FOR GREASY | | | WASTE SHALL COMPLY W/SPC SEC.921 FOR | | | HORIZONTAL COMBINATION WASTE AND VENT | | | SYSTEM. | | | | | | 7)AN OVERFLOW IS REQD.ON THE CONDENSATE | | | SYSTEM PRIOR TO THE CONNECTION WITH | | | THE STORM DRAINAGE SYSTEM OR CONNECTION | | | SHALL BE INDIRECT.SPC 804.3,806. | | | | | | CALL 561-569-8096,EXT.8377 IF YOU HAVE | | | ANY QUESTIONS. | | | TIMOTHY LARGE | | | PLUMBING PLANS EXAMINER. |
|