| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | ***********DENIED*********************** | | | | | | 1. PROVIDE AIR BALANCE SCHEDULE SHOWING | | | COMPLIANCE W/ 1997 SMC 501.2 | | | 2. DUCTS PENETRATING RATED WALLS TO HAVE | | | FIRE DAMPERS PER 1997 SMC 610.1.2 | | | PROVIDE LOCATION AND DETAILS OF FIRE | | | DAMPERS PER 610.6 (2 HR WALLS, SEE LS | | | PLAN |
|