Plan Review Notes
Plan Review Notes For Permit 00061369
Permit Number 00061369
Review Stop M
Sequence Number 3
Notes
Date Text
2001-01-08 00:00:00***********DENIED***********************
  
 1. PROVIDE AIR BALANCE SCHEDULE SHOWING
 COMPLIANCE W/ 1997 SMC 501.2
 2. DUCTS PENETRATING RATED WALLS TO HAVE
 FIRE DAMPERS PER 1997 SMC 610.1.2
 PROVIDE LOCATION AND DETAILS OF FIRE
 DAMPERS PER 610.6 (2 HR WALLS, SEE LS
 PLAN