Plan Review Notes
Plan Review Notes For Permit 00061369
Permit Number 00061369
Review Stop FIRE
Sequence Number 3
Notes
Date Text
2001-01-08 00:00:001) PROVIDE DETAILS ON WATER CURTAIN AND
 DRAFT STOP PLANNED FOR FLOOR OPENING
 BETWEEN SECOND AND THIRD FLOOR. THESE
 DETAILS SHOULD SHOW FIRE SPRINKLER AND
 DRAFT STOPPING TOGETHER.
 2) STANDPIPE SYSTEM STILL NOT SHOWN.
 PLEASE SHOW STANDPIPE SYSTEM CONNECTIONS
 FOR BUILDING.
 3) PROVIDE COMPLETE FIRE ALARM SYSTEM
 SHOP DRAWINGS FOR THE FIRE ALARM
 EQUIPMENT SHOWN FOR EXHIBITION HALL.
 PLEASE BE ADVISED THAT FRED GRINER OF
 CITY PLACE AGREED TO PROVIDE VOICE
 EVACUATION FOR THE FIRE ALARM SYSTEM
 WHEN THE EXHIBITION HALL WAS FITTED
 UP. PLEASE INDICATE THIS ON FUTURE
 PLANS. CUT SHEETS NEEDED ON ALL DEVICES
 PLANNED FOR USE.
 4) WATER CURTAIN FOR NORTHEAST STAIRWAY
 NOT SHOWN.
 5) GAS INSTALLATION TO COMPLY WITH
 NFPA 54.
 APPROVED PROVISO: