| Plan Review Notes For Permit 00061369 |
| Permit Number |
00061369 |
|
| Review Stop |
FIRE |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | 1) PROVIDE DETAILS ON WATER CURTAIN AND | | | DRAFT STOP PLANNED FOR FLOOR OPENING | | | BETWEEN SECOND AND THIRD FLOOR. THESE | | | DETAILS SHOULD SHOW FIRE SPRINKLER AND | | | DRAFT STOPPING TOGETHER. | | | 2) STANDPIPE SYSTEM STILL NOT SHOWN. | | | PLEASE SHOW STANDPIPE SYSTEM CONNECTIONS | | | FOR BUILDING. | | | 3) PROVIDE COMPLETE FIRE ALARM SYSTEM | | | SHOP DRAWINGS FOR THE FIRE ALARM | | | EQUIPMENT SHOWN FOR EXHIBITION HALL. | | | PLEASE BE ADVISED THAT FRED GRINER OF | | | CITY PLACE AGREED TO PROVIDE VOICE | | | EVACUATION FOR THE FIRE ALARM SYSTEM | | | WHEN THE EXHIBITION HALL WAS FITTED | | | UP. PLEASE INDICATE THIS ON FUTURE | | | PLANS. CUT SHEETS NEEDED ON ALL DEVICES | | | PLANNED FOR USE. | | | 4) WATER CURTAIN FOR NORTHEAST STAIRWAY | | | NOT SHOWN. | | | 5) GAS INSTALLATION TO COMPLY WITH | | | NFPA 54. | | | APPROVED PROVISO: |
|